V230 Self-Operated Pressure Regulating Valve

Instructions for use:
V230V231 type self-operated pressure (differential pressure) regulating valve, which is composed of valve body, valve seat, valve core components and other parts, is an energy-saving product that directly relies on the pressure change of the adjusted medium itself to automatically adjust the pressure without additional energy, and can be used for non-corrosive (good high temperature 350 degrees Celsius) pressure device for liquids, gases and steam and other media. It is widely used in petroleum, chemical, metallurgical, light industry and other industrial sectors, as well as urban heating and heating systems.

Product features:
Self-operated pressure regulating valves do not require additional energy and can work in places without electricity and gas, which is convenient and energy-saving.
The pressure segment range is fine and intersecting, and the adjustment accuracy is high.
The pressure setpoint can be set continuously during operation.
For the pressure adjustment after the valve, the ratio of the pressure in front of the valve to the pressure behind the valve can be 10:1~10:8.
Rubber diaphragm detection, actuator measurement accuracy is high and action is sensitive.
The pressure balance mechanism is used to make the control valve responsive and precise control.

Specifications and technical parameters

Nominal diameter mm

15

20

25

32

40

50

65

80

100

125

150

200

250

 Rated flow factor KVS

3.2

5

8

12.5

20

32

50

80

125

160

320

450

630

 Nominal pressure MPa

1.6 ; 4.0

 Z-value

0.6

0.6

0.6

0.55

0.55

0.5

0.5

0.45

0.4

0.35

0.3

0.2

0.2

 Very high
 Job
 Temperature °C

V230 V231

 liquid ≤ 140 ; Gas ≤ 80

 Hard-sealed V230

 Equipped with isolation tank≤ 200

 With isolation tank and extension≤ 300*

 Comes with isolation tank and heat sink≤ 200

 Pressure balancing element

 Bellows

 Rolling diaphragm

 French standard

 DIA (flange standard also available upon request)

 Valve body material

 PN16 : Cast iron (operating temperature ≤ 200 °C);
PN4.0 : Cast steel, cast stainless steel (operating temperature ≤ 350 °C)

 Valve core material

 stainless steel; The soft seal is stainless steel inlaid with rubber rings

 Very high working pressure MPa

Nominal pressure (pay attention to △ Pmax and the relationship between working pressure and operating temperature)

Notes:
1. The valve is reversed when the liquid > is 140 °C and the gas > is 80 °C;
2. Z-value: noise measurement coefficient, this value is used to measure the noise level, the specific calculation is detailed in the selection guide of self-operated control valve.

Overall dimensions and weight
V230/V231 control valve size and weight

Nominal diameter mm

20

25

32

40

50

65

80

100

125

150

200

250

L mm

150

160

180

200

230

290

310

350

400

480

600

730

B mm

212

238

238

240

240

275

275

380

380

295

325

372

 Approximate weight kg

6.7

9.7

13

14

17

29

33

60

70

80

140

220

D02 (D04) Actuator Size and Weight

Effective area cm2

32

80

250

630

D mm

172

172

263

380

H mm

435

430

470

520

 Approximate weight kg

7.5

7.5

13

28

Ordering instructions
The name and model of the regulating valve
Nominal pressure Mpa
Nominal Diameter (mm)
Rated flow factor (Kv)
Inherent flow characteristics
Media Name
Operating temperature and range
The mode of operation of the whole machine
pressure set point and adjustment range
Valve body, valve trim and packing material
Attached attachments